450/750V PVC Insulated PVC Sheathed Braid Screened Control Cable

450-750V PVC Insulated Braid Screened PVC Sheathed Control Cable Drawing

APPLICATION
Copper Conductor PVC Insulated PVC Sheathed Copper Wire Braid ( CWB ) Screened Rigid Control Cable (KVVP) is mainly used for system connection wire of control,signal,protection or measuring for rated voltage up to and including 450/750V.

CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
Code Name
KVVP
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation/Braid Screened/PVC Sheathed

CONSTRUCTION
Conductor
Preferred Number of cores:
2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/A according to IEC
Metallic Screened
Copper Wire Braid ( CWB )
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST1 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke,as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Max.temperature of conductor under short circuit-(Max.Duration 5 sec.)
PVC Insulated:160℃
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: 6 times of cable diameter

Nominal Cross Sectional Area(mm²)No. of CoresClass of ConductorMax.D.C.Resistance at 20℃(Ω/km):PlainMax.D.C.Resistance at 20℃(Ω/km):Metal-coated
0.5////
0.752-61124.524.8
0.752-61224.524.8
12-61118.118.2
12-61218.118.2
1.52-61112.112.2
1.52-61212.112.2
2.52-6117.417.56
2.52-6127.417.56
42-1414.614.7
42-1424.614.7
62-1413.083.11
62-1423.083.11
102-1021.831.84