26/35KV YJV22-Copper Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable

26-35KV YJV22-Copper Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable 02

APPLICATION
YJV22-Copper Conductor XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable.
Copper XLPE STA Armoured Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJV22
Rated Voltage (Uo/U)
26/35KV
Cable Structure
Copper Conductor/XLPE Insulation/Steel Tape Armoured/PVC Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen
Armoured Layer
Steel Tape

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥15D
For Single Core Cable————————————-≥20D

Nominal Cross Sectional Area (mm²)NO. of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
50110.543.72600
70110.545.22890
95110.547.13270
120110.548.73600
150110.550.54020
185110.5524410
240110.554.75110
300110.557.15900
400110.560.56340
500110.565.68380
630110.569.29790
50310.588.68700
70310.5929690
95310.586.311050
120310.599.712210
150310.5103.313560
185310.510714880
240310.5112.517210
300310.5117.719760
400310.5125.123390