IEC 60227 75 (RVVY) Oil Resistant PVC Sheathed Unscreened Flexible Cable

300/500V Oil Resistant PVC Sheathed Unscreened Flexible Cable

APPLICATION
IEC 60227 75 (RVVY) Oil Resistant PVC Sheathed Unscreened Flexible Cable.
IEC 60227 75 of hook up wire is also used in Industrial machinery,Heating and air-conditioning systems,Machine tools, dry/damp and wet interiors (including water-oil mixtures), but not for outdoor use.

CABLE STANDARDS
IEC60227,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
IEC Standard Code Name
60227 IEC 75
Rated Voltage (Uo/U)
300/500V
Cable Structure
Flexible CU/PVC Insulation/PVC Inner Sheath/PVC Over Sheath

CONSTRUCTION
Conductor
Number of cores:2~60 or other multi-core on request.
Preferred number of conductors: 2, 3, 4, 5, 6, 7, 12, 18, 27, 36, 48 and 60.
The conductors shall comply with the requirement given in IEC 60228 for class 5.
Insulation
PVC(Polyvinyl Chloride) Type PVC/D according to IEC
Over Sheath
PVC(Polyvinyl Chloride) Type PVC/ST9 according to IEC

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
D≤25mm——————≥4D
D>25mm——————≥6D

Nominal Cross Sectional Area(mm²)NO. of CoresClass of ConductorMax.Overall Diameter (mm)
0.5256.6
0.75257.2
1257.5
1.5258.6
2.52510.3
0.5357
0.75357.6
1358
1.5359.4
2.53511.2
0.5457.9
0.75458.3
1458.7
1.54510.2
2.54512.5
0.5558.6
0.75559.3
1559.8
1.55511.4
2.55513.7
0.5659.6
0.756510.1
16510.8
1.56512.6
2.56515.1
0.57510.4
0.757511.3
17511.8
1.57514.4
2.57516.8
0.512512.9
0.7512513.7
112514.6
1.512517
2.512520.6
0.518515.3
0.7518516.4
118517.2
1.518520.3
2.518524.8
0.527518.6
0.7527519.9
127521
1.527524.9
2.527530.2
0.536520.9
0.7536522.4
136523.8
1.536528.2
2.536534.2
0.548524.3
0.7548525.9
148527.6
1.548532.5
2.548539.1
0.560526.6
0.7560528.7
160530.5
1.560535.8
2.560542.6
Related Products