8.7/15KV YJLHV32-Aluminum Alloy Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable

Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable 3.6/6KV-26/35KV

APPLICATION
YJLHV32-Aluminum Alloy Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power Cable.
AAAC XLPE SWA Armoured Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJLHV32
Rated Voltage (Uo/U)
8.7/10KV、8.7/15KV
Cable Structure
Aluminum Alloy Conductor/XLPE Insulation/PVC Inner Sheath/Steel Wire Armoured/PVC Outer Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyvinyl Chloride) according to IEC
Metal Screen
Copper Tape Screen
Armoured Layer
Steel Wire

CHARACTERISTICS
Conductor Temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit Temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation Temperature
Ambient temperature under installation shall not be below 0℃
Minimum Bending Radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥10D
For Single Core Cable————————————-≥15D

Nominal Cross Sectional Area(mm²)No.of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
2514.5291587
3514.5301704
5014.531.51839
7014.5332002
9514.534.92220
12014.537.52770
15014.539.12907
18514.540.83124
24014.543.13485
30014.545.73877
40014.548.94396
50014.552.65018
63014.556.65746
2534.552.44378
3534.555.74740
5034.558.95222
7034.562.65815
9534.566.46501
12034.569.97068
15034.573.77814
18534.577.38510
24034.584.210650
30034.589.511934
40034.596.813756
50034.5104.515836
63034.5112.618105
Related Products