450/750V XLPE Insulated Steel Tape Armoured PVC Sheathed Control Cable

450-750V XLPE Insulated Steel Tape Armoured PVC Sheathed Multi-Core Control Cable Sectional Drawing

APPLICATION
Copper Conductor XLPE Insulated PVC Sheathed Steel Armoured Control Cable (KYJV22) is mainly used for system connection wire of control,signal, protection or measuring for rated voltage up to and including 450/750V.

CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
Code Name
KYJV22
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/XLPE Insulation/PVC Inner Sheath/Steel TapeArmoured/Outer PVC Sheath

CONSTRUCTION
Conductor
Preferred Number of cores:
2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
Cross-linked Polyethylene XLPE according to IEC
Screened
Steel Tape
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST2 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke( LSZH ),as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Max.temperature of conductor under short circuit-(Max.Duration 5 sec.)
XLPE Insulated:250℃
Preferred Permissible bending radius
For Armoured XLPE insulated cable not less than: 12 times of cable diameter

Nominal Cross Sectional Area(mm²)No. of CoresClass of ConductorMax.D.C.Resistance at 20℃(Ω/km):PlainMax.D.C.Resistance at 20℃(Ω/km):Metal-coated
0.757-61124.24 24.8
17-61118.118.18
1.57-61112.112.2
2.54-6117.417.56
44-1414.614.7
64-1413.083.11
104-1021.831.84
Related Products